Product Detail

Three-phase multi-function meter DSZ14WDRS-3X5A

we focus on four core areas

  • R&D and manufacturing of smart energy and water meters

  • IoT communication equipment development

  • Intelligent metering system design and operation

  • Cloud-based analysis of water and electricity consumption data

Share This Items :

DIN-rail three-phase multifunctional energy meter DSZ14WDRS-3x5A has passed the EU metrological certification MID certification (0120/SGS0314), with the advantages of compact size, high precision, good reliability, easy installation, etc. It adopts DIN35mm DIN-rail mounting structure, LCD display, measuring electric energy and other electric parameters, with compound rate metering, electric energy pulse output, power outage, key wake-up, electricity auto-feeding, LCD backlight display and other functions. It has the functions of compound rate metering, power pulse output, power failure, key wake-up, automatic power feeding, LCD backlight display and so on.

CT ratio setting function can match: 5:5,50:5,100:5,200:5,250:5,300:5,400:5,500:5,600:5,750:5,1000:5,1250:5,1500:5 and so on many kinds of ratio current transformer; There is RS-485 bus interface, can connect the corresponding bus equipment, large current It is suitable for places where direct access energy meters cannot meet the demand and places with poor wireless signal coverage or no network coverage.

With DIN35mm rail mounting, width of 4 modules.
Three-phase power metering with double-rate metering.
LCD display with low power consumption.
Real-time measurement of electrical parameters, such as voltage, current, power, etc..
With passive optoelectronic isolation type, power pulse test output function.
With power failure display function, and does not use batteries, with environmentally friendly supercapacitor, in the absence of power supply, LCD can be displayed twice a day for two weeks.
Error information (false), with current reverse, loss of voltage / phase alarm indication function, when the phase is missing or current direction error “false” and the corresponding phase line will be displayed on the liquid display, at the same time the LCD backlight will be the same frequency blinking.
Extendable with RS485 communication interface.
The amount of power is displayed by means of a flashing bar with a frequency of 10 imp/kWh.
Various CT variations can be set by applying jumpers.
Translated with DeepL.com (free version)

Wire Requirements m㎡
L 16
N 16
SO 6

Since the product works in a strong electrical environment, only certified or skilled electricians can install this electronic equipment, otherwise there is a risk of fire or electric shock!

1. Electrical parameters

volumetric L*W*H rated voltage rated current Rated frequency Starting current pulse constant accuracy Line power consumption
Pa(VA)
L:82 3×220/380V 10(80) 50Hz 0.04lb 1000 Level 1 <0.5VA
W:72
H:64

2、Maximum Allowable Tolerance

current value power factor(cosΦ) percentage error(%)
0.05lb 1 ±1.0
0.1lb 0.5L ±0.5
0.8C ±0.5
0.1lb~Imax 1 ±0.5
0.2lb~Imax 0.5L ±0.5
0.8C ±0.5

III. Technical parameters

performances parameters
LCD display content reticulation Single-phase two-wire
input voltage Rating AC220V,400V
Overload preservation:120%,
momentary:200%/10s
Power Consumption < 0.5VA(per phase)
Impedance > 300kΩ
Precision RMS measurements,0.2V
electric current rating AC:10-80A
overloaded preservation:120%,
momentary:200%/10s
Power Consumption < 0.5VA (per phase)
Impedance > 20mΩ
Precision RMS measurements,0.2V
frequency 40-60Hz, accuracy 0.1Hz
functionality Active 1
electricity With power metering
demonstrate Real time: electrical energy, voltage, current, power
compound rate Multiple CT change settings
pulse output 1 channel active pulse, optocoupler isolated
digital interface RS485 connector
operating temperature -10-55℃